Technical Specifications:
- Display LED Nixie Tube
- Operation Panel Silicon Rubber
- Digital Input 2
- Relay Output 5(Two Transistor Outputs)
- Analogue Input 1
- AC System 1P2W
- Alternator Voltage (30~360)V(ph-N)
- Alternator Frequency 50/60Hz
- Programmable Interface LINK
- Case Dimensions(mm) 95*86*46.5
- Panel Cutout(mm) 78*66
- Operating Temp. (-25~+70)℃
PERFORMANCE AND CHARACTERS1.Collecting single phase voltage of mains and generator, which suit for 50Hz/60Hz AC system
2.Switchable displayed parameters:
Mains voltage (V)
Generator voltage (V)
Engine cylinder temperature (℃)
Generator frequency (Hz)
Battery voltage (V)
Accumulated running time(H)
3.With mains electricity monitoring and AMF functions
4.Protection function for generator under/over volt, under/over frequency, low oil pressure, and fail to start protection functions; when in protection, LED indicates alarm, and goes shutdown protection
5.Using stepper motor and programmable outputs to control air flap (close/open air flap according to the cylinder temperature)
6.Speed signals derive from ignition coil primary (diode need to be in series)
7.Three crank disconnect conditions can be optional (generator frequency, speed, and speed + gen frequency)
8.2 discrete inputs, which default set as remote start input and low oil pressure input
9.3 fixed relay outputs (fuel output, start output and ignition control)
10.2 programmable transistor outputs, which can be set as common alarm output, ETS control, idle control , preheat control, close GCB output, close MCB output and air flap blocked output
11.LINK communi 12.Nixie tube and LED display with button-press operation
13.Modular design, anti-flaming ABS plastic enclosure, embedded installation way; compact structure with easy mounting;