System type can set as: S1 (Mains) & S2 (Mains), S1 (Mains) & S2 (Generator), S1 (Generator) & S2 (Mains), S1 (Generator) & S2 (Generator).
-
132x64 LCD with backlight, multilingual interface (including English, Chinese or other languages), push-button operation.
-
Collect and display 2-way 3-phase Voltage, Frequency and Phase.
-
Collect and display Active Power, Reactive Power, Apparent Power, Power Factor and Current.
-
S1/S2 separated over current warning/ trip alarm.
-
NEL (Non-essential Load) trip function.
-
Display S1/S2 Total kW Energy, Total kvar Energy, Total Close Times.
-
Display continuous power supply time and S1/S2 total power supply time.
-
Sync Transfer function; in addition, Voltage Difference, Frequency Difference and Phase Difference can be displayed.
-
For Stored-Energy type ATS, its close relay will active after the PF Input is active.
-
Over/under voltage, loss of phase, reverse phase sequence, over/under frequency protection.
-
Phase Sequence Transfer function.
-
Automatic/Manual mode. In manual mode, can force the switch to close or open;
-
All parameters can be set on site. Passwords authentication ensures authorized staff operation only.
-
The genset can be Manual Test on site to achieve start/stop operation.
-
ATS Controller has function of automatic Re-closing.
-
Closing output signal can be set as on intervals or as continuous output.
-
Applicable for PC Three-stage, PC Two-stage, CB and CC switch.
-
Applicable for 2 isolated neutral line.
-
Real-time clock (RTC); Event log Function (Event log can record 99 items circularly).
-
Scheduled Run & Scheduled Not Run (can be set as start genset once a day/week/month whether with load or not).
-
Can control two generators to work as Cycle Run mode, Master Run mode and Balance Run mode.
-
Widely power supply range DC(8~35)V allows the controller can bear 80V instantaneous current.
-
Large terminal space allows the controller can bear maximum 625V input voltage.
-
With RS485 isolated communication interface. With "remote controlling, remote measuring, remote communication, remote regulating" function by the ModBus communication protocol. Can remote start/stop the genset and remote control the ATS to close or open.
-
Suitable for various AC systems (3 phase 4-wires, 3-phase 3-wires, single-phase 2-wire, and 2-phase 3-wire).
-
Modular design, self extinguishing ABS plastic shell, pluggable terminal, built-in mounting,compact structure with easy installation.